Please enter the words you want to search for:

[Return to folder listing]

   Experiment of a wind generator participation to frequency control   [View] 
 [Download] 
 Author(s)   V. COURTECUISSE; M. EL MOKADEM; C. SAUDEMONT; B. ROBYNS; J. DEUSE 
 Abstract   In this paper, a primary frequency control strategy based on fuzzy logic designed for variable speed wind generators is proposed and tested on a 2,2 kW test bench. The fuzzy logic supervisor ensures a regular primary reserve on a large range of wind speed without any wind speed measurement. This supervisor controls simultaneously the generator torque and the pitch angle to keep the primary reserve; it determines in real time the generator power reference value. The fuzzy logic supervisor is compared with a classical strategy which maximises the power efficiency.The experiments point out the regularity of the power reserve and the ability to contribute to frequency control. 
 Download 
Filename:Unnamed file
Filesize:737.8 KB
 Type   Members Only 
 Date   Last modified 2008-04-10 by System