Fault Ride-through Capability Implementation in Wind Turbine Converters Using a Decoupled Double Synchronous Reference Frame PLL
| [View]
[Download]
|
Author(s) |
IOV Florin; RODRIGUEZ P.; BLAABJERG Frede; LUNA A.; TEODORESCU Remus |
Abstract |
This work exploits the Decoupled Double Synchronous Reference Frame PLL (DDSRF-PLL) as an effective method for grid synchronization of WT's power converters in the presence of transient faults in the grid. The DDSRF-PLL uses a dual synchronous reference frame and a decoupling network to effectively separate the positive- and negative-sequence voltage components in a fast and accurate way. Excellent behavior of the DDSRF-PLL is demonstrated experimentally. Once sequence components of the faulty grid voltage are properly identified several algorithms computing current references are developed. Additionally, different power delivery strategies to ride-through grid faults are discussed and simulations results are presented. As a conclusion, it will be demonstrated that certain control strategies ensure a stable operation of the front-end inverter while the grid voltage is supported by means of injection of instantaneous reactive power at the same time. |
Download |
Filename: | 0955-epe2007-full-13272987.pdf |
Filesize: | 1.326 MB |
|
Type |
Members Only |
Date |
Last modified 2008-01-11 by System |
|
|