Please enter the words you want to search for:

[Return to folder listing]

   Three Phase Four Wires LC Coupled Shunt Active Power Filter (APF): New topology and control   [View] 
 [Download] 
 Author(s)   LAMICH Manuel; BALCELLS Josep; GONZALEZ David; GAGO Javier 
 Abstract   This paper presents a new structure and control method for three phase four wires LC coupled parallel active power filters (APF) for harmonics cancellation. The main differential point with regard to other structures used in the past consists of the connection of neutral wire to negative of DC bus in the inverter, thus avoiding the need of split capacitors at the DC bus. The LC coupling and a particular control of the DC voltage at the coupling C allow the use of low voltage at the DC bus and provide a symmetry of available voltage, in the current controller, during ton and toff. The paper includes a general discussion of the new structure, comparing it with the classical L coupled shunt APFs and presents the control method to obtain the above mentioned voltage symmetry, which allows lower DC bus voltage and lower values of coupling L. Simulation and experimental results are given to show the behavior of the system, used for harmonics cancellation.  
 Download 
Filename:0677-epe2007-full-09373564.pdf
Filesize:423.3 KB
 Type   Members Only 
 Date   Last modified 2008-01-11 by System