   Improved Voltage and Frequency Restoration in Parallel Connected Three Phase Power Converters   [View] 
 [Download] 
 Author(s)   U. B. Jensen; F. Blaabjerg; J. K. Pedersen 
 Abstract   In parallel-connected converter systems load sharing is often achieved by adjusting the voltage amplitude and the frequency depending on the load. Due to this adjustment the steady state frequency and voltage amplitude differ from their reference depending on the load. This paper presents a new method that provides load sharing in the transient phase with restoration of the steady state values. The method is proved both by simulation and experiments in a 400 Hz AC system. 