Please enter the words you want to search for:

[Return to folder listing]

   Control of a Doubly-fed Induction Wind Generator Under Unbalanced Grid Voltage Conditions   [View] 
 [Download] 
 Author(s)   BREKKEN Ted; MOHAN Ned 
 Abstract   Wind energy is often installed in rural, remote areas characterized by weak, unbalanced power transmission grids. In induction wind generators, unbalanced three-phase stator voltages cause a number of problems, such as overheating, over-current, and stress on the mechanical components from torque pulsations. Therefore, beyond a certain amount of unbalance, induction wind generators are switched out of the network. This can further weaken the grid. In doubly-fed induction generators, control of rotor currents allows for adjustable speed operation and reactive power control. In addition, it is possible to control the rotor currents to correct for the problems caused by unbalanced stator voltages, including torque pulsations and unbalanced stator currents. This paper presents a novel voltage mode controller design for a doubly-fed induction generator that provides variable speed, reactive power control. Also, under stator voltage unbalance conditions, the proposed control eliminates torque pulsations and draws more balanced currents from the utility. 
 Download 
Filename:0198
Filesize:424.5 KB
 Type   Members Only 
 Date   Last modified 2006-02-05 by System