   Using Load Zero Sequence Voltage To Eliminate Source Zero Sequence Current   [View] 
 [Download] 
 Author(s)   M. Fathi 
 Abstract   The zero sequence voltage of the load affects the source during the process of instantaneous inactive or reactive power compensation. Different approaches have been used to overcome this issue. This synopsis initially reviews the minimization method, which divides the load currents into its active and reactive components and find them by solving an optimization problem. The active current is supplied by the source, while the reactive current is managed by the compensator. However, when load voltages contain zero sequence component, then zero sequence current is imposed to the source. To tackle this issue, load zero sequence voltage is measured and a complementary way is presented such that eliminates the source zero sequence current. The converter power circuit as well as the control circuit is simulated to show the effectiveness of the approach. 