Analysis of a 1.7 MVA Doubly Fed Wind-Power Induction Generator during Power Systems Disturbances
| [View]
[Download]
|
Author(s) |
S. Seman; J. Niiranen; S. Kanerva; A. Arkkio |
Abstract |
The performance of a 1.7 MVA wind-power doubly fed induction generator (DFIG) under network fault is studied using simulator developed in MATLAB-Simulink. The simulator consists of the DFIG analytical model, the detailed frequency converter model including passive crowbar protection, and model of the transformer. The rotor-side frequency converter is controlled by a modified direct torque control (DTC). Simulation results show the transient behavior of the doubly fed induction generator when a sudden voltage dip is introduced with and
without the crowbar implemented. |
Download |
Filename: | Unnamed file |
Filesize: | 504.2 KB |
|
Type |
Members Only |
Date |
Last modified 2006-01-24 by System |
|
|