   Control of a three-phase active power filter using a time-variant conductance model   [View] 
 [Download] 
 Author(s)   T. Yoshida; M. Yamakawa; O. Miyashita 
 Abstract   A new method for controlling a three-phase active power filter (APF) using a time-variant conductance model is proposed. The control strategy is not based on the coordinate transformation but on the simple conductance circuit model. This model provides a current reference so that the APF neutralizes the harmonic components of the load currents in the three-wire electrical power system. Applying this method to a four-wire power distribution system practically eliminates the neutral-line current. Experimental and simulation results verify the usefulness of the method. 