Please enter the words you want to search for:

[Return to folder listing]

   Passivity Design for LCL-Type Grid-Connected Inverter Based on PCC Voltage Feedforward Control   [View] 
 [Download] 
 Author(s)   Shaojie LI, Hua LIN, Xingwei WANG 
 Abstract   In this article, the admittance model for LCL-type grid-connected inverter with proportional PCC voltage feedforward control is built to design the passivity. It is found that if the LCL parameters are designed in a certain range, i.e., _rsup._s/6 and _L1Cinf._s/3 (_r is the resonance frequency of the LCL filter, _L1C is the resonance frequency of the inverter-side inductor and the filter capacitor and _s is the sampling frequency), the passivity can be achieved while the grid background harmonics can also be well suppressed. The simulation and experimental results verify the correctness of the theoretical analysis. 
 Download 
Filename:0074-epe2023-full-05281814.pdf
Filesize:2.67 MB
 Type   Members Only 
 Date   Last modified 2023-09-24 by System