   Comparison between DC Voltage Droop Schemes and Grid-Following & Grid-Forming Control in AC Systems in View of Interoperability of MTDC grids   [View] 
 [Download] 
 Author(s)   Kosei SHINODA, Mohamed ELSODANY, Juan-Carlos GONZALEZ, Jing DAI, Abdelkrim BENCHAIB, Seddik BACHA 
 Abstract   This paper explores the fundamental characteristics of two typical DC voltage droop controlschemes, namely the direct droop where the power setpoint is adjusted in proportion to the DC-voltage deviation, and the inverse droop where the DC-voltage setpoint is adjusted in proportion to the power deviation. We draw an analogy between these two droop controls for DC voltage regulation and and the grid-following and grid-forming controls in AC systems. Simulation results show that, forthe security of the DC grid, it is crucial to specify the desired characteristics of droop-controlled stations in both steady state and transient. 