Comparison between DC Voltage Droop Schemes and Grid-Following & Grid-Forming Control in AC Systems in View of Interoperability of MTDC grids
| [View]
[Download]
|
Author(s) |
Kosei SHINODA, Mohamed ELSODANY, Juan-Carlos GONZALEZ, Jing DAI, Abdelkrim BENCHAIB, Seddik BACHA |
Abstract |
This paper explores the fundamental characteristics of two typical DC voltage droop controlschemes, namely the direct droop where the power setpoint is adjusted in proportion to the DC-voltage deviation, and the inverse droop where the DC-voltage setpoint is adjusted in proportion to the power deviation. We draw an analogy between these two droop controls for DC voltage regulation and and the grid-following and grid-forming controls in AC systems. Simulation results show that, forthe security of the DC grid, it is crucial to specify the desired characteristics of droop-controlled stations in both steady state and transient. |
Download |
Filename: | 0347-epe2023-full-15493563.pdf |
Filesize: | 1009 KB |
|
Type |
Members Only |
Date |
Last modified 2023-09-24 by System |
|
|