Abstract |
This paper presents a modular multilevel STATCOM with partially rated energy storage configured insub-stacks based on full bridge multi busbar Sub-module (SM). The soft-paralleling mechanism anddoubled paths increase the current limit. The lower level controller of the proposed topology is detailed introduced and the performances are compared with a conventional single-busbar full bridge STATCOM controlled by classic SM sorting based low level controller. When providing reactive power compensation, power losses is reduced by 14.9\%, and the maximum SM voltage deviation is reduced by 35.2\%, while active power capability is further improved from power factor = 0.5 to power factor = 0.7 with the proposed control framework of the MBSM STATCOM. |