   Control strategy for reducing inrush current in three-phase UPS system   [View] 
 [Download] 
 Author(s)   S. Nishikata; S. Kuroda; T. Kataoka 
 Abstract   Control strategy for reducing inrush current when a load of capacitor-filtered rectifier is connected to a three-phase UPS system is proposed. Inrush current can be greatly reduced when digital control with inrush current suppression loop in addition to observer, voltage drop compensator and PID controller is applied to the system. Transient responses of UPS output voltage and load current when the load is connected are shown, and the usefulness of the proposed control is verified with simulations and experiments. 