Abstract |
The capacitor voltage positive-feedback is a widely extended active damping strategy. It can effectively damp the LCL output filter resonant poles for low ratios of resonance to sampling frequencies. However, the existing delays in the control loop limit the applicability of the capacitor-voltage positive-feedback. For high ratios of resonance to sampling frequencies, it becomes ineffective and can even destabilize the system. This limitation is overcome in this paper by adjusting the delay in the feedback path. With the delay adjustment, a robust damping can be achieved if the delays are properly considered, including the filters, and the grid impedance variations are taken into account. Simulation results validate the proposed active damping strategy. |