A COST-EFFECTIVE DC/DC-CONVERTER WITH INTEGRATED UPS-FUNCTION | ||||||
Author(s) | Berthold Fuld | |||||
Abstract | A new DC/DC-converter with integrated UPS-function is described. The solution has important advantages compared to other UPS-approaches: - Minimized number of conversion stages - Very high efficiency during battery operation - No interruption at line failure - Small volume - Low cost A conventional DC/DC-converter is supplemented by a second input winding of the transformer, a second switch-circuit and a charge circuit. Only one control circuit for both inputs is necessary: the change from line to battery operation is natural. At battery operation only one conversion stage between battery and load is necessary, this gives a very high efficiency. The charge circuit can be realized as a simple buck-stage, for converters with 50% max. duty cycle it must work in the discontinuous mode.The same winding of the transformer as for battery operation is used. Simulation results show the function of the system. |
|||||
Download |
|
|||||
Type | Members Only | |||||
Date | Last modified 2019-06-03 by System | |||||
![]() |