   Flicker mitigation, Application to a STATCOM   [View] 
 [Download] 
 Author(s)   G. De PrĂ©ville 
 Abstract   Flicker, caused by large fluctuating loads as arc furnace, is one of the power quality problems that include interruptions, voltage sags and dips, harmonics. The state of the art technology to reduce flicker is shunt compensation using Static Var Compensator with thyristors. However, this kind of technology has an intrinsic limited flicker mitigation capability. Traditionally, flicker is mainly due to reactive power fluctuation. However, Flicker generation is more complicated and in the paper, drop voltage and shunt compensation methods are described step by step to explain flicker. Simulations of arc furnace installation with shunt compensation device using Voltage Source Converter or STATCOM with its control are presented. Multilevel structure simulation is shown. Reduction of PST versus shunt compensation methods is shown. 