   Reduction of DC-link current harmonics for Three-phase VSI over Wide Power Factor Range using Single-Carrier-Comparison Discontinuous PWM   [View] 
 [Download] 
 Author(s)   Koroku NISHIZAWA 
 Abstract   This paper proposes a novel discontinuous PWM (DPWM) in order to reduce dc-link current harmonics of a voltage source inverter (VSI) over wide load-power-factor range. This modulation method, which requires only one carrier, contributes to a lifetime extension of smoothing capacitors in a motor drive system. Furthermore, by realizing this modulation method with only one carrier, a high cost hardware such as a field-programmable gate array (FPGA) is not necessary. By adding an offset to voltage references of conventional DPWM, and shifting two unclamped voltage references in every half control period, the dc-link current harmonics are reduced even when load power factor changes. It is clarified by experiments that the proposed DPWM reduces the dc-link current harmonics by 18.4\% at most at modulation index of 0.705 and load power factor of 0.819. 