Please enter the words you want to search for:

[Return to folder listing]

   DC Short Circuit Ride-through Strategy for a Full-Bridge MMC HVDC Transmission System   [View] 
 [Download] 
 Author(s)   Mahmoud FAWZI 
 Abstract   Modular multi-level converters (MMC) are considered a promising topology for HV applications likeHVDC transmission systems. Such systems must be designed to provide high reliability against differenttypes of faults. MMCs using Half-Bridge (HF) cells are well known for lacking the capability to blockshort circuits in the DC link. On the contrary, Full-Bridge (FB) cells can block the short circuit currentin the DC link, they also enable the implementation of Fault Ride-through (FRT) functionalities, as thecells can generate bipolar voltages in this case. This paper presents a DC short circuit fault ride-throughstrategy for HVDC transmission system using an MMC topology with FB cells (FBMMC). Two modesof operation are possible during the fault. In the _rst one, the MMC can support the AC grid with reactivepower, but will not transfer active power. In the second mode, the MMC can transfer active power duringthe fault. 
 Download 
Filename:0200-epe2017-full-23381505.pdf
Filesize:1.895 MB
 Type   Members Only 
 Date   Last modified 2018-04-17 by System