Please enter the words you want to search for:

[Return to folder listing]

   Current and Speed Sensor FDIR for a DFIM Grid Connected Variable Speed Pumped Storage System   [View] 
 [Download] 
 Author(s)   Amel DAMDOUM 
 Abstract   This paper proposes Fault Detection, Isolation and Reconfiguration (FDIR) techniques to realize the connection of a DFIM pumped storage system with the grid in the presence of current and speed sensor failures. For the detection method authors use the parity space approach either for current sensor failure or the rotation speed one. The proposed reconfiguration techniques exploit stator flux estimation using existing stator current and voltage measurements. All studied system (DFIM pumped storage and grid) with proposed FDIR strategy is simulated using PSIM software. Next, simulations and experimental results are given to validate the synchronization phase in healthy conditions and to demonstrate the effectiveness of the proposed detection method to isolate the faulty sensor and to guarantee the satisfactory behavior of this system. 
 Download 
Filename:0387-epe2017-full-23165164.pdf
Filesize:695.6 KB
 Type   Members Only 
 Date   Last modified 2018-04-17 by System