 Author(s)   Hongyang ZHANG 
 Abstract   The current from an electrical arc furnace (EAF) in a steel plant is highly unsymmetrical, i.e. it comprises a large amount of negative sequence. This causes problems with the voltage stability in the capacitor submodules for a static synchronous compensator (STATCOM), when implemented using the modular multilevel converter (M2C) concept.In order to counteract the uncontrollability of the capacitor voltage, a common practice is to circulate a zero-sequence fundamental current or a direct current. The method brings the benefit of re-balancing the active power among the individual phases while it requires over-rating of the valve current or dc voltage of the STATCOM. This would in practice give a more expensive design.This paper presents a benchmark of various M2C-based STATCOM designs considering the valve overrating. The STATCOM topologies will be benchmarked with the EAF modeled for all possible combinations of positive- and negative-sequence current. The rating comparison considering the dc capacitor ripple and zero-sequence harmonic injection are discussed. 
 Download 
Filename:0334-epe2016-full-22504148.pdf
Filesize:1.522 MB
 Type   Members Only 
 Date   Last modified 2017-04-13 by System