Cell Capacitor Sizing in Modular Multilevel Converters and Hybrid Topologies
| [View]
[Download]
|
Author(s) |
Michael MERLIN, Timothy GREEN, Paul MITCHESON, FRANCISCO JOSE MORENO, Kevin DYKE, David TRAINER |
Abstract |
This paper presents a method to calculate the minimal size of cell capacitors in multilevel VSCs which meets a maximum voltage deviation criterion under ideal conditions. This method is applied to the Modular Multilevel Converter (MMC), the Alternate Arm Converter (AAC) and the hybrid multilevel converter with ac-side cascaded H-bridge cells (AC-CHB). The results show that the newer VSC topologies exhibits smaller energy deviation in their stacks, leading to an overall smaller volume of cell capacitors for the converter station but often accompanied by some compromises such as higher power losses or degraded DC current waveform quality. |
Download |
Filename: | 0426-epe2014-full-23553000.pdf |
Filesize: | 729.8 KB |
|
Type |
Members Only |
Date |
Last modified 2015-06-08 by System |
|
|