 Author(s)   Ivan ANDRADE, Ramon BLASCO-GIMENEZ, Ruben PENA 
 Abstract   This paper includes the theoretical analysis and experimental validation of a control strategy for the direct powerand current control of grid-connected inverters. The studied control strategy allows for constant active and reactive power delivery during unsymmetrical faults and with supply voltage distortion, without the use of a PLL or FLL.It has been proven that only positive sequence current harmonics are necessary to deliver constant P and Q during unbalanced grid faults. The resulting stationary frame control has been experimentally validated during unbalanced voltage sags and swells. 