Voltage balancing control in 3-Level Neutral-Point Clamped Converters using triangular carrier PWM modulation for FACTS applications
| [View]
[Download]
|
Author(s) |
Javier CHIVITE-ZABALZA, Pedro IZURZA, Gorka CALVO, Miguel RODRIGUEZ-VIDAL |
Abstract |
In this paper, a novel technique to balance the voltage of the two split dc capacitors of a 3-Level Neutral-Point-Clamped inverter using triangular carrier PWM modulation is presented. This technique, suitable for reactive power compensation and for inverters operating with a relatively low switching frequency, consists in adding a square wave at six times the output frequency. Subsequently, the paper presents a comparison with two already known strategies in which a sinusoidal waveform at two and six times the output frequency are injected. The current contribution to the mid-point of the dc bus is then analysed for different modulation indexes and operating conditions. Based on this analysis, a small-signal averaged model, suitable for control design purposes is presented. Finally, simulation and experimental results on a 690 V AC, 120 kVA test bench that validate the theory are shown. |
Download |
Filename: | 0185-epe2011-full-11500950.pdf |
Filesize: | 2.363 MB |
|
Type |
Members Only |
Date |
Last modified 2012-01-26 by System |
|
|