DC-link Voltage Oscillations Reduction During Unbalanced Grid Faults for High Power Wind Turbines
| [View]
[Download]
|
Author(s) |
Hernan MIRANDA, Remus TEODORESCU, Pedro RODRIGUEZ, Lars HELLE |
Abstract |
During unbalanced grid voltage faults the Power injected to the grid experiences 100Hz oscillations as a result of interactions between positive and negative sequence components of three-phase voltages and currents. These oscillations can become as high as \%50 percent of the rated power. In this article an improved controller is proposed which present different behavior during normal operation and faults to keep track of non-sinusoidal current reference signals. The reference signals are calculated to obtain zero power oscillations. Reconfigurable resonant controllers are used for this purpose applied to 3-level Neutral-point-clamped converter in the megawatt range. |