UNCONTROLLED RECTIFIERS FOR HVDC CONNECTION OF LARGE OFF-SHORE WIND FARMS
| [View]
[Download]
|
Author(s) |
Ramon BLASCO-GIMENEZ, Salvador ANYO-VILLALBA, Johel RODRIGUEZ, Francisco MORANT, Soledad BERNAL |
Abstract |
Modern wind turbines allow for tight control of terminal voltage, this is particularly true for synchronous generator (SG) based wind turbines. Therefore, an integrated design of wind turbine and HVDC link control can lead to a substantial simplification of the off-shore rectifier. This paper introduces an integrated control algorithm for line commutated thyristor (LCT) based HVDC transmission line whereby the off-shore rectifier tap changer is eliminated and a cheaper and more efficient uncontrolled rectifier is used instead of a LCT-based rectifier. The presented control strategy allows for good performance during steady state and transient operation, including on-shore fault ride-through operation. |
Download |
Filename: | 0581-epe2009-full-00253154.pdf |
Filesize: | 264.5 KB |
|
Type |
Members Only |
Date |
Last modified 2010-01-27 by System |
|
|